Can I put a low-voltage transformer in the attic?
I'm planning a low-voltage monorail light system,
fitted with 10x 7.5W 12V AC LED light heads. The manufacturer provides a "remote electronic transformer", and the installation instructions call for "remote but accessible location" for the transformer.
Can I put such transformer in the attic space above the room?
The attic is insulated, so the transformer will likely need an additional
enclosure box (like this)
I looked up the California Electrical Code 2016 but couldn't find a paragraph which would explicitly allow or disallow such installation (and everything <1000V is considered low-voltage by the code, which doesn't help with search)
Besides, the attic space gets quite hot during the summer, and the
transformer has a thermal shut-off. So maybe it is not a good idea
to put it there anyway.
The alternative option I have is to install the transformer inside a closet
nearby, but again I'm not sure whether this would be allowed by code.
electrical lighting led low-voltage
add a comment |
I'm planning a low-voltage monorail light system,
fitted with 10x 7.5W 12V AC LED light heads. The manufacturer provides a "remote electronic transformer", and the installation instructions call for "remote but accessible location" for the transformer.
Can I put such transformer in the attic space above the room?
The attic is insulated, so the transformer will likely need an additional
enclosure box (like this)
I looked up the California Electrical Code 2016 but couldn't find a paragraph which would explicitly allow or disallow such installation (and everything <1000V is considered low-voltage by the code, which doesn't help with search)
Besides, the attic space gets quite hot during the summer, and the
transformer has a thermal shut-off. So maybe it is not a good idea
to put it there anyway.
The alternative option I have is to install the transformer inside a closet
nearby, but again I'm not sure whether this would be allowed by code.
electrical lighting led low-voltage
Being over 55W, the low voltage exemptions won't fully apply.
– Harper
Dec 26 '18 at 20:13
add a comment |
I'm planning a low-voltage monorail light system,
fitted with 10x 7.5W 12V AC LED light heads. The manufacturer provides a "remote electronic transformer", and the installation instructions call for "remote but accessible location" for the transformer.
Can I put such transformer in the attic space above the room?
The attic is insulated, so the transformer will likely need an additional
enclosure box (like this)
I looked up the California Electrical Code 2016 but couldn't find a paragraph which would explicitly allow or disallow such installation (and everything <1000V is considered low-voltage by the code, which doesn't help with search)
Besides, the attic space gets quite hot during the summer, and the
transformer has a thermal shut-off. So maybe it is not a good idea
to put it there anyway.
The alternative option I have is to install the transformer inside a closet
nearby, but again I'm not sure whether this would be allowed by code.
electrical lighting led low-voltage
I'm planning a low-voltage monorail light system,
fitted with 10x 7.5W 12V AC LED light heads. The manufacturer provides a "remote electronic transformer", and the installation instructions call for "remote but accessible location" for the transformer.
Can I put such transformer in the attic space above the room?
The attic is insulated, so the transformer will likely need an additional
enclosure box (like this)
I looked up the California Electrical Code 2016 but couldn't find a paragraph which would explicitly allow or disallow such installation (and everything <1000V is considered low-voltage by the code, which doesn't help with search)
Besides, the attic space gets quite hot during the summer, and the
transformer has a thermal shut-off. So maybe it is not a good idea
to put it there anyway.
The alternative option I have is to install the transformer inside a closet
nearby, but again I'm not sure whether this would be allowed by code.
electrical lighting led low-voltage
electrical lighting led low-voltage
asked Dec 26 '18 at 18:50
user2907934user2907934
162
162
Being over 55W, the low voltage exemptions won't fully apply.
– Harper
Dec 26 '18 at 20:13
add a comment |
Being over 55W, the low voltage exemptions won't fully apply.
– Harper
Dec 26 '18 at 20:13
Being over 55W, the low voltage exemptions won't fully apply.
– Harper
Dec 26 '18 at 20:13
Being over 55W, the low voltage exemptions won't fully apply.
– Harper
Dec 26 '18 at 20:13
add a comment |
2 Answers
2
active
oldest
votes
Your attic is an accessible location that looks like it is already housed so all you will need a box for the connection to the power according to the instructions. Additional enclosures should not be needed.
add a comment |
The term "low voltage" is used differently in different contexts. In this case the low voltage part is the 12VAC output of the transformer supplying the monorail.
The transformer in your link is in an enclosure that can be mounted anywhere you can get to it without cutting drywall or otherwise ripping something apart to get to it. Your attic would be fine from an accessibility standpoint but so would your closet. It would not be OK to install it between the studs in a wall you're building, then sheetrock the wall so you can't get to it any more.
Although the spec sheet on the link page doesn't have operating temperature info, it's likely that the transformer is rated for attic temperatures, but you'd have to contact the manufacturer for that information.
add a comment |
Your Answer
StackExchange.ready(function() {
var channelOptions = {
tags: "".split(" "),
id: "73"
};
initTagRenderer("".split(" "), "".split(" "), channelOptions);
StackExchange.using("externalEditor", function() {
// Have to fire editor after snippets, if snippets enabled
if (StackExchange.settings.snippets.snippetsEnabled) {
StackExchange.using("snippets", function() {
createEditor();
});
}
else {
createEditor();
}
});
function createEditor() {
StackExchange.prepareEditor({
heartbeatType: 'answer',
autoActivateHeartbeat: false,
convertImagesToLinks: false,
noModals: true,
showLowRepImageUploadWarning: true,
reputationToPostImages: null,
bindNavPrevention: true,
postfix: "",
imageUploader: {
brandingHtml: "Powered by u003ca class="icon-imgur-white" href="https://imgur.com/"u003eu003c/au003e",
contentPolicyHtml: "User contributions licensed under u003ca href="https://creativecommons.org/licenses/by-sa/3.0/"u003ecc by-sa 3.0 with attribution requiredu003c/au003e u003ca href="https://stackoverflow.com/legal/content-policy"u003e(content policy)u003c/au003e",
allowUrls: true
},
noCode: true, onDemand: true,
discardSelector: ".discard-answer"
,immediatelyShowMarkdownHelp:true
});
}
});
Sign up or log in
StackExchange.ready(function () {
StackExchange.helpers.onClickDraftSave('#login-link');
});
Sign up using Google
Sign up using Facebook
Sign up using Email and Password
Post as a guest
Required, but never shown
StackExchange.ready(
function () {
StackExchange.openid.initPostLogin('.new-post-login', 'https%3a%2f%2fdiy.stackexchange.com%2fquestions%2f153439%2fcan-i-put-a-low-voltage-transformer-in-the-attic%23new-answer', 'question_page');
}
);
Post as a guest
Required, but never shown
2 Answers
2
active
oldest
votes
2 Answers
2
active
oldest
votes
active
oldest
votes
active
oldest
votes
Your attic is an accessible location that looks like it is already housed so all you will need a box for the connection to the power according to the instructions. Additional enclosures should not be needed.
add a comment |
Your attic is an accessible location that looks like it is already housed so all you will need a box for the connection to the power according to the instructions. Additional enclosures should not be needed.
add a comment |
Your attic is an accessible location that looks like it is already housed so all you will need a box for the connection to the power according to the instructions. Additional enclosures should not be needed.
Your attic is an accessible location that looks like it is already housed so all you will need a box for the connection to the power according to the instructions. Additional enclosures should not be needed.
answered Dec 26 '18 at 19:26
Ed BealEd Beal
31.2k12145
31.2k12145
add a comment |
add a comment |
The term "low voltage" is used differently in different contexts. In this case the low voltage part is the 12VAC output of the transformer supplying the monorail.
The transformer in your link is in an enclosure that can be mounted anywhere you can get to it without cutting drywall or otherwise ripping something apart to get to it. Your attic would be fine from an accessibility standpoint but so would your closet. It would not be OK to install it between the studs in a wall you're building, then sheetrock the wall so you can't get to it any more.
Although the spec sheet on the link page doesn't have operating temperature info, it's likely that the transformer is rated for attic temperatures, but you'd have to contact the manufacturer for that information.
add a comment |
The term "low voltage" is used differently in different contexts. In this case the low voltage part is the 12VAC output of the transformer supplying the monorail.
The transformer in your link is in an enclosure that can be mounted anywhere you can get to it without cutting drywall or otherwise ripping something apart to get to it. Your attic would be fine from an accessibility standpoint but so would your closet. It would not be OK to install it between the studs in a wall you're building, then sheetrock the wall so you can't get to it any more.
Although the spec sheet on the link page doesn't have operating temperature info, it's likely that the transformer is rated for attic temperatures, but you'd have to contact the manufacturer for that information.
add a comment |
The term "low voltage" is used differently in different contexts. In this case the low voltage part is the 12VAC output of the transformer supplying the monorail.
The transformer in your link is in an enclosure that can be mounted anywhere you can get to it without cutting drywall or otherwise ripping something apart to get to it. Your attic would be fine from an accessibility standpoint but so would your closet. It would not be OK to install it between the studs in a wall you're building, then sheetrock the wall so you can't get to it any more.
Although the spec sheet on the link page doesn't have operating temperature info, it's likely that the transformer is rated for attic temperatures, but you'd have to contact the manufacturer for that information.
The term "low voltage" is used differently in different contexts. In this case the low voltage part is the 12VAC output of the transformer supplying the monorail.
The transformer in your link is in an enclosure that can be mounted anywhere you can get to it without cutting drywall or otherwise ripping something apart to get to it. Your attic would be fine from an accessibility standpoint but so would your closet. It would not be OK to install it between the studs in a wall you're building, then sheetrock the wall so you can't get to it any more.
Although the spec sheet on the link page doesn't have operating temperature info, it's likely that the transformer is rated for attic temperatures, but you'd have to contact the manufacturer for that information.
answered Dec 26 '18 at 19:34
batsplatstersonbatsplatsterson
10k11229
10k11229
add a comment |
add a comment |
Thanks for contributing an answer to Home Improvement Stack Exchange!
- Please be sure to answer the question. Provide details and share your research!
But avoid …
- Asking for help, clarification, or responding to other answers.
- Making statements based on opinion; back them up with references or personal experience.
To learn more, see our tips on writing great answers.
Some of your past answers have not been well-received, and you're in danger of being blocked from answering.
Please pay close attention to the following guidance:
- Please be sure to answer the question. Provide details and share your research!
But avoid …
- Asking for help, clarification, or responding to other answers.
- Making statements based on opinion; back them up with references or personal experience.
To learn more, see our tips on writing great answers.
Sign up or log in
StackExchange.ready(function () {
StackExchange.helpers.onClickDraftSave('#login-link');
});
Sign up using Google
Sign up using Facebook
Sign up using Email and Password
Post as a guest
Required, but never shown
StackExchange.ready(
function () {
StackExchange.openid.initPostLogin('.new-post-login', 'https%3a%2f%2fdiy.stackexchange.com%2fquestions%2f153439%2fcan-i-put-a-low-voltage-transformer-in-the-attic%23new-answer', 'question_page');
}
);
Post as a guest
Required, but never shown
Sign up or log in
StackExchange.ready(function () {
StackExchange.helpers.onClickDraftSave('#login-link');
});
Sign up using Google
Sign up using Facebook
Sign up using Email and Password
Post as a guest
Required, but never shown
Sign up or log in
StackExchange.ready(function () {
StackExchange.helpers.onClickDraftSave('#login-link');
});
Sign up using Google
Sign up using Facebook
Sign up using Email and Password
Post as a guest
Required, but never shown
Sign up or log in
StackExchange.ready(function () {
StackExchange.helpers.onClickDraftSave('#login-link');
});
Sign up using Google
Sign up using Facebook
Sign up using Email and Password
Sign up using Google
Sign up using Facebook
Sign up using Email and Password
Post as a guest
Required, but never shown
Required, but never shown
Required, but never shown
Required, but never shown
Required, but never shown
Required, but never shown
Required, but never shown
Required, but never shown
Required, but never shown
Being over 55W, the low voltage exemptions won't fully apply.
– Harper
Dec 26 '18 at 20:13